When your medium voltage drive trips without warning and the plant floor goes quiet, the losses start adding up immediately. Understanding why medium voltage drive failures happen is the first step toward preventing them.
Many common failures are preventable. The key is knowing where to look and being proactive before a minor issue turns into a catastrophic shutdown.
Why Do Medium Voltage Drives Fail Unexpectedly?
Medium voltage variable frequency drives are built to run for years, but they do fail (that’s how we make a living)! They often operate in harsh industrial environments and depend on components that wear out over time. When maintenance lapses or environmental conditions deteriorate, your likelihood of failures increases dramatically.
The failures that surprise you most are usually the ones that have developed slowly: A capacitor slowly leaking, a connection loosening from vibration, a cooling fan not moving enough air because of bearings or contaminants. Often, these conditions do not trigger alarms until the damage is done.
How Does Capacitor Degradation Cause VFD Failure?

Electrolytic capacitors are the primary component within the DC bus on many medium voltage drives. They filter AC ripple and store the energy the inverter section draws from to create the output. After 7 to 10 years of operation, the electrolyte inside these capacitors dries out, reducing their ability to hold charge.
As capacitance drops, ripple current increases. That excess ripple causes heat on the capacitor itself, heats surrounding components, and can create drive faults or even catch fire! Film and oil-filled capacitors used in some medium voltage VFD topologies last longer, but they still degrade over time.
If your drive is past the 10-year mark and you have not replaced the electrolytic capacitors, you are operating on borrowed time.
What Role Do Loose Connections Play in Drive Failures?
Loose connections are one of the most frequent causes of medium voltage drive failure, and one of the easiest to prevent. Vibration gradually loosens both power and control connections over time.
When a power connection loosens, arcing begins. That arc produces heat and oxide buildup, which further degrades the contact surface. Eventually the connection fails entirely, sometimes with catastrophic results.
Loose control connections are even harder to track down. They cause intermittent, erratic signals to the drive controller, producing faults that seem random. Torquing all connections to specification during preventative maintenance is a must.
How Does the Operating Environment Shorten Drive Life?
Your medium voltage VFD is an electronic system operating in an industrial facility, and heat, humidity, dust, and airborne contaminants can all affect how it operates.
High ambient temperatures accelerate capacitor aging and push semiconductors closer to their thermal limits. For every 10°C above the recommended operating range, electronic component life can drop by roughly half. Facilities running drives in enclosed areas with poor ventilation face this problem frequently.

Moisture corrodes circuit boards and control connections. In water and wastewater treatment plants, humidity gets pulled into the drive cabinet through the cooling system, creating conditions for corrosion and tracking across insulation surfaces. Dust and metallic particles can short circuit or block cooling airflow entirely.
Why Are Cooling System Failures So Dangerous for VFDs?
The switching components inside a medium voltage VFD generate significant heat during normal operation.
When cooling fans fail or degrade, that heat is unable to be dissipated. The result is premature aging of every heat-sensitive component in the drive. In many cases, the drive will trip on an overtemperature fault. In worse cases, components fail before the temperature alarm triggers.
Cooling fans on medium voltage drives are typically run by 230V or 480V three-phase motors. They can often be tested independently of the medium voltage supply, making them straightforward to check during scheduled maintenance.
EMA field service engineers inspect cooling systems as a standard part of every site visit. A failed fan left unaddressed will eventually take the whole drive down.
How Does Power Supply Drift Cause Failures?
Every medium voltage drive contains low-voltage power supplies (12V, 15V, 24V, and other combinations) that feed the internal controllers, gate drivers, and communication boards. These power supplies depend on their own set of electrolytic capacitors for filtering.
When those capacitors degrade, the power supply output drifts out of tolerance. Modern VFD controllers are sensitive to voltage variation, and even a small drift can produce intermittent faults or erratic drive behavior that is extremely difficult to diagnose.
What About Transformer Failures?
Multi-pulse transformers integrated into medium voltage drives can fail from insulation breakdown, overheating, or arcing caused by vibration. These transformers sit upstream of the converter and inverter sections, so they are often overlooked during routine maintenance.
A transformer that hums louder than normal or has discolored windings is sending you a clear warning. Lead times on transformers have gotten extremely high, so we’ve seen transformer failures make the entire drive beyond economical repair.

Can Proactive Maintenance Prevent Unexpected Drive Failures?
Yes. A structured preventative maintenance program addresses nearly every failure covered in this article. Facilities that follow a regular PM schedule experience significantly fewer unplanned shutdowns compared to facilities relying on reactive maintenance alone.
A proper medium voltage VFD PM includes torquing all connections, inspecting cooling fans, verifying power supply tolerances, and reviewing fault history and trended data. Capacitors and transformers also need visual inspection for signs of degradation.
EMA has performed preventative maintenance on VFDs for over 35 years. Our trained technicians know what to look for because we see the failure patterns every day.
For facilities that want eyes on their drives between PM visits, EMA offers DriveScan. This remote monitoring tool alerts you when things drift out of normal range before a catastrophic failure occurs.
Take Action Before Your Medium Voltage Drive Fails
Unexpected medium voltage drive failures often result from a preventable condition: aging capacitors, loose connections, heat buildup, or neglected cooling systems. The good news is that each of these conditions can be greatly reduced by proactive maintenance and monitoring.
If your medium voltage VFD is past the 10-year mark, if you are seeing intermittent faults, or if you want a second set of experienced eyes on your drive, EMA is ready to help. We have over 35 years of hands-on medium voltage drive experience on every major manufacturer.