Medium Voltage Drives (VFD) are usually on critical applications. An annual preventive maintenance (PM) is very worthwhile.
Preventive Maintenance on medium voltage variable frequency drives (VFD s) is often complicated by the various design architectures employed by different manufacturers.
The two most obvious differences, are whether the medium voltage VFD is a current source or voltage source medium voltage VFD. Both have have some form of electrolytic capacitors either in the DC link circuit or in power supplies or driver circuits within various parts of the MV VFD. The electrolytic capacitors are just one reason that medium voltage VFD s need preventive maintenance.
Siemens (Robicon), for example, uses electrolytic DC buss capacitors in their DC link circuit. These have roughly a 5 year life span before they start failing.
The life span of electrolytic capacitors is dictated by temperature, mounting clamp tightness and exposure to over-voltage situations. As the buss capacitors get weaker their ability to filter AC ripple diminishes. During a PM, EMA service engineers will check the buss ripple voltage on the VFD and determine if it is within the tolerance level specified by the manufacturer. We check buss ripple on the power supplies (+24V, +5V, +15V, -15V, 10V etc) to make sure they are within specifications.
If the degradation of the buss capacitors and power supply capacitors are recognized early enough during PM of the MV VFD, measures can be taken to prevent catastrophic failures. A typical repair on a medium voltage drive can be very expensive. In fact, some of our competitors require a PO of $70K just to show up on emergency service calls. (We do not at EMA)
Below are five other things that need to be addressed during a PM of a medium voltage VFD.
Spare parts: Because of the critical nature of MV VFD applications, most manufacturers offer spare parts with a MV VFD sale. As an end user, it is critical that those spare parts are in good shape when you need them.
Electrolytic capacitors that sits on the shelf for more than a year are recommended to be reformed before being put into a VFD especially the buss capacitors, hence it is very important to perform PM at a minimum of annually.
According to IEEE, electrical systems that are not subjected to Preventive maintenance are three times more likely to experience failure than those that are. It is recommended that service engineers rotate the spare cell/parts on a yearly basis. After a long shelf life the capacitors in the cells need to be reformed. By rotating cells during the yearly PM basis we can avoid the need to reform the caps should the emergency exist where the cell needs to be used.
Operation of the Switchgear: Due to the higher energy levels that are present on most medium voltage drives, there are major handshakes that are implemented between the switch gear and the VFD. Typically the VFD needs to know if the switch gear is READY and OPEN and there is NO FAULT before it will request closure on the switchgear. Typically a service engineer will verify the proper functioning of the handshake between the switchgear and MV VFD. This is normally accomplished by applying control voltage and turning off the MV feed. The I/Os of the MV VFD can set to test the functionality of the switchgear. During this process, the grounding bars can be verified to make sure they are properly positioned when the switch gear is in an off condition.
Per IEEE, 30% of all electrical failures are due to loose connections. We verify trip set points and make sure that both the drive and mechanical setting are set.
Megging the motor: Megging a MV motor will show if there is bad insulation either on the cables between the MV VFD and the motor, or internal within the motor. It is recommended to test a 4160V motor with a 5KV megger.
Readings of less than 5 Giga Ohms could indicate bad insulation, a bad motor, or moisture inside the motor. We recommend megging the motor from the wires on the output of the MV VFD. The MV VFD should be disconnected and isolated completely from the motor when you do this.
Cleaning the MV VFD: Clean all dirt and dust off the MV VFD and make sure there is no moisture left in the unit. Use compressed air if you wish, but be certain that moisture is not introduced. Dirt and moisture at voltage levels of 4160V could potentially create small arcs in the VFD.
In addition, the airflow filters and blowers/fans should be verified. The blower direction in particular should be noted.
Verify and adjust parameter set for optimum performance: The final step would be to verify that parameters are set correctly for optimum performance of the MV VFD and motor. During this time, service engineers will need to collect data with an oscilloscope and amp meters. This is a potentially dangerous step, and only qualified personnel should perform this task. Verified output waveforms and buss ripples and make adjustment on the parameter for proper and optimum performance of the MV VFD.
The report from a medium voltage VFD PM should be detailed enough to provide tracking data over time. If the ripple was at a certain level a year ago, and is higher now, then that would indicate component degradation. Same for other measurements.
Many people would perhaps argue that for smaller variable frequency drives on non-critical applications, the cost justification for yearly preventive maintenance might be problematic.
However, on medium voltage variable frequency drives, that is seldom an issue. Medium Voltage VFD repair is costly, and downtime even more so. And, the repairs themselves can take time.
Preventive Maintenance on medium voltage VFD s is a great investment.